Voltage:
380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional)
Frequency:
50Hz / 60Hz, ± 5%
By-pass voltage:
380/400 VAC 3P + N , 4 Wires, ± 10%
Voltage distortion:
≤ 10%
Protection:
Fuses, Voltage & Frequency tolerance, Input power lim
Voltage :
380/400 VAC 3 Phase + N , ± 1% (415 optional)
Other protections:
Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
Voltage THD :
< 3% (at 100% linear load)
Type:
VRLA AGM / GEL / NiCd
Float / End of discharge voltage:
±
Battery cabinet:
External
Battery ambient temperature:
25º
Protections:
3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
Automatic testing:
Standard every 72 hours (adjustable)
Standards:
EN62040-1, EN62040-2, EN62040-3
User interface:
TFT panel, 5 vector buttons, Buzzer,
Indicators:
P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
Advanced :
Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication:
2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs:
EPO input, Interactive battery panel input, Genset input
Genset kit:
Standard (programmable)
Dimensions (mm) HxWxD:
1900x880x775 1900x1250x775 2040x1250x840
OPTIONS:
Different input / output voltage
T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients:
Adaptors
USB Alarm Logger, TCP/IP ,GSM/G:
Parallel operation
up to 8:
(*) Depending on power and input/output conditions