Thông số sản phẩm
Voltage:
380/400 VAC 3P + N + G ± 20% (415 VAC +15%, - 25% optional)
Frequency:
50Hz / 60Hz, ± 5%
By-pass voltage:
380/400 VAC 3 Phase + N , 4 Wires, ± 10%
Voltage distortion:
≤ 10%
Protection:
Fuses, Voltage & Frequency tolerance, Input p
Voltage :
380/400 VAC 3 P + N , ± 1% (415 VAC optional )
Frequency tolerance:
Line synchronized: ± 2% / Free running: ± 0,1%
Overload protection:
100% - 125% load: 10 min, 125% - 150% load: 1 min, - > 150% load: by pass
Other protections:
Advanced short circuit, Voltage tolerance, DC balance, Regenerative load, Current limiting
Voltage THD:
< 3% (at 100% linear load)
Type:
VRLA AGM / GEL / NiCd
Float / End of discharge voltage:
±
Battery cabinet:
Internal
External:
Battery ambient temperature
3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional):
Automatic testing
Standard every 72 hours (adjustable):
GENERAL
Standards:
EN62040-1, EN62040-2, EN62040-3
User interface:
4 lines LCD panel, Mimic leds, 5 vector buttons, Buzzer, Optional TFT panel
Indicators:
P-N voltage, P-P voltage, Current, Power, Crest Factor, Frequency, PF, Service Time
:
Self diagnostics, 3 maintenance time indicators, Calibration over RS232,operating hour meter
Communication:
2xRS232 serial ports, 4 standard and 8 optional DRY contact alarm relays
Inputs:
EPO input, Interactive battery panel input, Genset input
Genset kit:
Standard (programmable)
Software:
T-Mon Admin Multi UPS monitoring 10-50-100-200 clients, T-Mon Server 50-100-200 clients
Alarm logging:
Standard: 
Protections:
Power module over-temperature, Over current, Temperature high alarm
Temperature range:
0º
:
90% max. (non-condensing) 
68 dBA:
Weight without batteries (kg)
Dimensions (mm) HxWxD:
1040x400x815
Different input / output voltage:
Please ask
Transformer:
Galvanic isolation transformer at the input &
Adaptors:
SNMP, RS485, Remote monitoring panel, MODBUS (RS485 or TCP/IP), 
Parallel operation:
up to 8